SAM-e Installation and Operation Manual Includes installation, operation maintenance and troubleshooting information for your SAM-e and Mini
7 | Installation SAM-e In-Duct
SAM-e Installation | 8 Typical SAM-e Installation General SAM-e Assembly Diagram
9 | SAM-e Installation 1 Fasten support brackets to header using 5/16” washers and 5/16” nylon lock-nuts. 2 Place header on duct floor and
SAM-e Installation | 10 3 Insert tube into insertion stop washer and then into grommet. Wetting grommet with water will make assembly easier. E
11 | SAM-e Installation 5 Attach tube support bracket using supplied 1/4” lock-washer and 1/4” hex screws. 6 No mounting frame – proceed t
SAM-e Installation | 12 6A If no mounting frame is supplied: Attach bracket flanges to tube support bracket using 5/16” screws, washers, and nylon
13 | SAM-e Installation 7 Slide frame sides into frame base. 8 Attach Frame Pivot using 5/16” bolt, washer, and nylon lock-nut. Side V
SAM-e Installation | 14
15 | SAM-e Installation Installation in Vertical Duct
SAM-e Installation | 16 1 Complete assembly following Steps 1 through 8 on pages 9 through 13. Install complete assembly into duct at 10° angl
Thank you for choosing Nortec. Proprietary Notice This document and the information disclosed herein are proprietary
17 | SAM-e Installation Mini SAM-e Installation Procedures
SAM-e Installation | 18 Mini SAM-e Assembly General Installation
19 | SAM-e Installation 1 Place header into duct. Use supplied template to cut holes for steam and condensate parts. Attach header to duct using
SAM-e Installation | 20
21 | SAM-e Installation Plumbing
SAM-e Installation | 22 SAM-e with Pressure Steam Pressurized Plumbing with External Separator • Steam components in grey provided by Nortec. • T
23 | SAM-e Installation Pressurized Plumbing without External Separator Note: The SAM-e header functions as a steam separator, therefore an ext
SAM-e Installation | 24 Internal Baffle Plate
25 | SAM-e Installation Condensate Pump Plumbing When pressurized steam enters SAM-e, pressure drops down to almost atmospheric p
SAM-e Installation | 26 Mini SAM-e with Pressurized Steam Mini SAM-e Pressurized with External Separator • Steam components in grey provided by
Contents 2 Introduction 2 Location of Humidifier’s Manifold in an Air Conditioning System 4 Identify your Components 5 How to Use this M
27 | SAM-e Installation Mini SAM-e Pressurized without External Separator • Max steam pressure of 15 psig when no
SAM-e Installation | 28 Mini SAM-e Condensate Pump Plumbing When pressurized steam enters Mini SAM-e, pressure drops down
29 | SAM-e Installation SAM-e with Atmospheric Steam Atmospheric Plumbing Atmospheric steam inlet Use Nortec supplied steam hose and gear c
SAM-e Installation | 30 Plumbing with Drain Water Cooler 1" NPT to 3/4” NPT Reducer (Supplied By Others) 1" Air Gap To Prevent
31 | SAM-e Installation Mini SAM-e with Atmospheric Steam Mini SAM-e with Atmospheric Steam Atmospheric steam inlet Use Nortec supplied steam ho
SAM-e Installation | 32
33 | SAM-e Installation Atmospheric Steam Lines
SAM-e Installation | 34 Plumbing Pressurized SAM-e For pressurized steam line installation instructions, refer to LiveSteam Steam Injection Humidifie
35 | SAM-e Installation Electrode Steam-Line Table 1: Electrode Steam-Line Humidifier Steam output [ lb ] MED-L copper tube nominal steam line size
SAM-e Installation | 36 Gas Steam-Line Table 2: Gas Steam-Line Humidifier Steam output [ lb ] MED-L copper tube nominal steam line size Stainless st
1 | SAM-e Installation CAUTION: Plumbing Plumbing to be performed by a licensed plumber. Drain water from humidifier can be very hot. Do not
37 | SAM-e Installation SE Steam Line Table 3: SE Steam-Line Unit No. of Steam Outlets Steam output [ lb ] MED-L copper tube nominal steam line siz
SAM-e Installation | 38 NHRS Steam-Line Table 4: SE Steam-Line Humidifier Steam output [ lb ] MED-L copper tube nominal steam line size Stainless ste
39 | SAM-e Installation Effective Length of Typical Steam-Line Fittings Table 5: Effective length of Typical Steam-Line Fittings Nominal tube size St
SAM-e Installation | 40 Atmospheric SAM-e Condensate Drainage 1 SAM-e condensate outlet connection is male 3/4”-NPT. 2 Condensate from SAM-e must b
41 | SAM-e Installation Steam Lines and Condensate Returns Use appropriate slope Figure 1: Slope Figure 2: Insulate pipe
SAM-e Installation | 42 Figure 4: Distributor Above Humidifier (Copper Steam Line) Figure 5: Distributor Above Humidifier (Hose)
43 | SAM-e Installation Figure 6: Steam Distributor Below Humidifier (Hose) Figure 7: Steam Distributor Below Humidifier and Obstruction (Hose)
SAM-e Installation | 44 Figure 8: Long Steam Run
45 | SAM-e Installation Atmospheric Steam Lines
SAM-e Installation | 46 Insulation Factory-Installed Insulation 1 Unpack tubes and headers. Inspect tubes to ensure that stainless insulation cove
SAM-e Installation | 2 Introduction Receiving and Unpacking Equipment Check packing slip to ensure ALL material has been delivered. Each humidifi
47 | SAM-e Installation Quantity of Insulating Covers Required to Cover SAM-e Tube Table 7: Quantity of Insulating Covers Required to Cover SAM-e Tub
SAM-e Installation | 48 Header Installation 1 Install header insulation for SAM-e; expand header insulation to fit over header and slide on. Ensur
49 | SAM-e Installation SAM-e Insulation Retrofit 1 Install header wrap around header. 2 Tuck header wrap underneath rubber grommets and
SAM-e Installation | 50 FOR DUAL INLETS; INSULATE HEADER AS SHOWN ON PREVIOUS PAGE. INSULATE SECOND INLET AS SHOWNROLL SHIELD TO CREATE OVERLAPDETAI
51 | SAM-e Installation 3 Apply shields to tubes and secure with stainless straps. 4 Completed Tube.
SAM-e Installation | 52 Mini SAM-e Insulation Retrofit 1 Connect Top and Bottom heat shields together (snap fit) . 2 Completed header.
53 | SAM-e Installation 3 Fit shields to tubes. 4 Secure with stainless straps.
SAM-e Installation | 54 5 Completed tube.
55 | SAM-e Installation Troubleshooting, Maintenance, Spare Parts
SAM-e Installation | 56 Troubleshooting Steam tubes discharge water: 1 Steam supply pipe is not insulated. 2 Steam supply pipe not properly drain
3 | SAM-e Installation Identify your Components
57 | SAM-e Installation Warranty Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY), warran
U.S.A. 1860 Renaissance Blvd. Sturtevant, WI 53177 826 Proctor Avenue Ogdensburg, NY 13669 CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7 TEL:
SAM-e Installation | 4 Identify your Optional Components
5 | SAM-e Installation How to Use this Manual SAM-e - In Duct Section 2 Follow steps 1-9 SAM-e - Vertical Duct Installation Section 4 Foll
SAM-e Installation | 6 Plumbing Section 6 6A - SAM-e Pressure Steam 6B - mini SAM-e Pressure Steam 6C - SAM-e Atmospheric Steam 6D - mini SAM-e Atmos